Voltage Sags Impact on CAR and SOR of HANARO

  • 발행 : 2004.10.28

초록

The reactor protection system (RPS) of HANARO is a safety class system. The reactor is tripped by dropping four shut off rods (SOR). The SOR system consists of a SOR, hydraulic pump, hydraulic cylinder, solenoid valves and a power supply unit which has the AC coil contactor as a switching component. The hydraulic pump lifts up the SOR. The SOR drops by loss of the hydraulic pressure in the hydraulic circuit at the occurrence of voltage sags or interruptions. From this experiment, we knew that the magnitude of the voltage sag which impacts on this system is 70V, 500msec. The reactor regulation system (RRS) of HANARO has four CARs which are connected to the driver through a magnetic clutch. The CAR drops by loss of electromagnetic force of the magnetic clutch when the deeper voltage sags to lower than 10V, 500msec.

키워드