Cooling and Heating Performance Evaluation of a Ground Source Heat Pump

지열원 열펌프의 냉.난방 성능 평가

  • 손병후 (한국건설기술연구원, 화재 및 설비 연구부) ;
  • 조정식 (한국건설기술연구원, 화재 및 설비 연구부) ;
  • 신현준 (한국건설기술연구원, 화재 및 설비 연구부) ;
  • 안형준 (코오롱건설(주) 기술연구소)
  • Published : 2004.04.28

Abstract

The main objective of the present study is to investigate the performance characteristics of a ground source heat pump (GSHP) system with a 130 m vertical 60.5 mm nominal diameter U-bend ground heat exchanger. In order to evaluate the performance analysis, the GSHP system connected to a test room with 90 $m^2$ floor area in the Korea Institute of Construction Technology ($37^{\circ}39'$ N, $126^{\circ}48'$ E) was designed and constructed. This GSHP system mainly consisted of ground heat exchanger, indoor heat pump and measuring devices. The cooling and heating loads of the test room were 5.5 and 7.2 kW at design conditions, respectively. The experimental results were obtained from July to January in cooling and heating season of $2003{\sim}2004$. The cooling and heating performance coefficients of the system were determined from the experimental results. The average cooling and heating COPs for the system were obtained to be 4.82 and 3.02, respectively. The temperature variations in ground and the ground heat exchanger surface at different depths were also measured.

Keywords