열원의 위치에 따른 평판형 히트파이프의 열적 성능

Thermal Performance of Flat-strip Heat Pipe with Various Heat Source Locations

  • 발행 : 2004.04.28

초록

A series of experiments was conducted to examine characteristics of a grooved flat-strip heat pipe having multiple heat sources. The inner grooves of the heat pipe have the aspect ratio of 1 to $2.5(0.42{\times}1.05$ mm) whose pitch was 0.6 mm. Four block heaters ($10{\times}20$ mm) were placed in the evaporator section at intervals of 20 mm and six different heating modes were tested. The maximum surface heat flux of 80 $W/cm^2$ was achieved while the operating temperature was kept below $100^{\circ}C$, In the nearest heating mode (from the condenser location), the heat pipe exhibited more stable temperature distribution than the far heating mode where the heaters is located furthest from the condenser.

키워드