$SF_6$ 상태에 따른 절연파괴전압 비교분석에 관한 연구

The analysis & comparative method on the breakdown voltage in $SF_6$

  • 발행 : 2004.11.03

초록

In this paper the experiments of insulation characteristics by temperature change of $SF_6$ gas and insulation characteristics about liquid $SF_6$ in GIS(Gas Insulated Switchgear) were described. From this result, at low temperature, the breakdown voltage was increased with a drop of temperature and an increase of the inner pressure in GIS. The ability of insulation in liquid $SF_6$ was higher than that of the highly pressurized $SF_6$ gas. A liquid $SF_6$ discharge characteristics was caused by bubble formed evaporation of liquid $SF_6$ and bubble when high voltage apply to electrode. Corona was happened to weak bubble and was proceed to new bubble breakdown.

키워드