Experimental Study on Heat Transfer Performance of Plate Type Absorber with Variation of Solution Flow Rate

용액유량에 따른 플레이트 흡수기의 흡수 열전달 특성 실험

  • Published : 2003.04.23

Abstract

An experimental study of the absorption process of water vapor into a lithium bromide solution was performed. For the purpose of development of high performance absorption chiller/hater utilizing lithium bromide solution as working fluid, it is the most effective to improve the performance of absorber with the largest heat transfer area of the four heat exchangers. The experimental apparatus was composed of a plate type absorber which can increase the heat exchange area per unit volume to investigate more detail characteristics instead of the conventional type, horizontal tube bundle type. The size of plate absorbers were made for $0.4m{\times}0.6m$ and the design object of a refrigeration capacity was lRT. In this experiment, three kind plate absorbers which were flat plate, dimple plate and groove plate were used. The results were less than the design object values, that is, the refrigeration capacity was about $0.3{\sim}0.4RT$ and the overall heat transfer coefficient was $500{\sim}600kcal/m^2h^{\circ}C$ at the standard conditions.

Keywords