Performance Variations of River Water Source Heat Pump System According to Heat Exchanger Capacity Variations

열교환기 용량변화에 따른 하천수열원 열펌프의 성능 변화

  • 박성룡 (한국에너지기술연구원 미활용에너지연구센터) ;
  • 백영진 (한국에너지기술연구원 미활용에너지연구센터) ;
  • 김희환 (공주대학교 기계공학과 대학원) ;
  • 이영수 (한국에너지기술연구원 미활용에너지연구센터)
  • Published : 2003.04.23

Abstract

The utilization of unused energy is important because it can afford to offer a chance to increase energy efficiency of a heat pump system. One of the promising unused energy sources is river water. It can be used as a heat source in both heating and cooling effectively with its superior features as a secondary working fluids. In this study, the performance of a 5HP heat pump system using river water as a heat source is investigated by both experiment and simulation. According to system simulation results, performance improvement of condenser seems more effective than that of evaporator for better $COP_H$. The serial connection is also preferred among several methods to improve plate type heat exchanger performance. The experimental results show that the hot water of $50{\sim}60^{\circ}C$ can be acquired from water heat source of $5{\sim}9^{\circ}C$ with $COP_H$ of $2.7{\sim}3.5$.

Keywords