Effects of fin pitch and array of the frost laver growth on extended surface of a heat exchanger

열교환기 표면에서의 서리층 성장에 대한 휜 피치와 배열의 영향

  • 양동근 (한양대학교 대학원 기계공학과) ;
  • 이관수 (한양대학교 기계공학부)
  • Published : 2003.04.23

Abstract

This paper presents the effects of the fin array and pitch on the frost layer growth of a heat exchanger. The numerical results are compared with experimental data of a cold plate to validate the present model, and agree well with experimental data within a maximum error of 8%. The characteristics of the frost formation on staggered fin array are somewhat different from those of in-line array. The frost layer at the first fin of the in-line array grows rapidly, compared to second fin, whereas the difference of the frost layer growth between the fins of the staggered array is small. For fin pitch below 10 mm, the frost layer growth of second fin in the staggered array is affected by that of first fin. The frost layer growth and heat transfer of single fin deteriorate with decreasing fin pitch regardless of fin array, however, the thermal performance of a heat exchanger, considering increase of heat surface area, becomes better.

Keywords