Parameter Effects on the Time to Reach Flashover Conditions in Single Room Fires

건물화재의 플래시오버 도달 시간에 영향을 미치는 인자들에 관한 연구

  • Published : 2003.04.23

Abstract

In structural fires, flashover is characterized by the rapid transition in fire behavior from localized burning of fuel to the involvement of all combustibles in the enclosure. An investigation of parameter effects on the time to reach flashover conditions in a typical single room fire is undertaken using a zone method (FAST) and Thomas method. Major parameters affecting the time to reach flashover are found to be fire growth rate, ventilation opening area and internal room surface. The results of the FAST and the Thomas Method give very similar results of the time to reach flashover..

Keywords