Piping Failure Analysis In Domestic Nuclear Safety Piping System

국내 안전등급 배관에 대한 손상사례 분석

  • 최선영 (한국원자력연구소 종합안전평가부) ;
  • 최영환 (한국원자력안전기술원 원자력안전연구실)
  • Published : 2003.04.23

Abstract

The purpose of this paper is to analyze piping failure trend of safety pipings In domestic nuclear power plants. First, database for the piping failure was constructed with 105 data fields. The database includes plant population data, event data, and service history data. 7 kinds of piping failures in domestic NPPs were investigated. Among the 7 cases, detailed root causes were investigated for 3 cases. The first one is pipe wall thinning in main feedwater pipings of Westinghouse 3 loop type plants. The root cause of the wall thinning was flow accelerated corrosion near welding area. The next one is leak event in chemical and volume control system(CVCS) due to vibration. Some cracks occurred in socket welding area. The events showed that the integrity or socket weld is very vulnerable to vibration. The last one is also a leak event in primary sampling line in Korean standard reactor due to thermal fatigue. Although the structural integrity was not maintained by the events, there was no effect on nuclear safety in the above 3 piping failure eases.