핀-관 열교환기에서 개별 열의 열전달 효과

Heat Transfer Performance of Individual Rows in Fin-Tube Heat Exchangers

  • 발행 : 2003.12.05

초록

An experimental study was performed to examine the heat transfer performance of individual rows of fin-tube heat exchangers. The heat transfer performance was measured using air-enthalpy type calorimeter. The examined heat exchangers consists of $7{\Phi}$ tube and fin patterns of them are slit and louver types. Equivalent fin spacing are 18 FPI for all samples, and the number of tube rows were 2. In order to confirm that thermal boundary condition on fins of each row are the same, physically separated between two rows as well as connected heat exchangers were used. The frontal air velocity varied from 0.7 to 2.5 m/s. Heat transfer performance for each row are measured. It was observed that the heat transfer coefficient of the 2nd row were smaller than that of the 1st row at low Reynolds number while larger at high Reynolds number.

키워드