A Modified Current Differential Relaying Algorithm for Transformer Protection Considered by a Remanent Flux

잔류자속을 고려한 변압기 보호용 수정 전류차동 계전방식

  • Kang, Y.C. (Chonbuk National University NPT Center) ;
  • Jin, E.S. (Chonbuk National University NPT Center) ;
  • Won, S.H. (Chonbuk National University NPT Center) ;
  • Lim, U.J. (Chonbuk National University NPT Center) ;
  • Kang, S.H. (Myongji University NPT Center)
  • 강용철 (전북대학교 차세대전력기술연구센터) ;
  • 김은숙 (전북대학교 차세대전력기술연구센터) ;
  • 원성호 (전북대학교 차세대전력기술연구센터) ;
  • 임의재 (전북대학교 차세대전력기술연구센터) ;
  • 강상희 (명지대학교 차세대전력기술연구센터)
  • Published : 2003.11.13

Abstract

During magnetic inrush or over-excitation saturation of the core in a transformer draws a large exciting current. This can cause mal-operation of a differential relay. This paper proposes a modified current differential relay for transformer protection. In order to cope with the remanent flux at the beginning. the start of saturation of the core is detected and the core flux at the instant is estimated by inserting the differential current into a magnetization curve. Then, this core flux value can be used to calculate the core flux. The proposed relay calculates the core-loss current from the induced voltage and the core-loss resistance; the relay calculates the magnetizing current from the core flux and the magnetization curve. Finally, the relay obtains the modified differential current by subtracting the core-loss current and the magnetizing current from the conventional differential current. The proposed technique not only discriminates magnetic inrush and over-excitation from an internal fault, but also improves the speed of the conventional relay.

Keywords