초록
Fall-of-potential method is used usually to measure the ground impedance of large scale grounding system exactly. Because the interlinked magnetic flux between closed loops to inject test current and to measure potential rise is existed in E-P-C straight line arrangement, mutual(or inductive) coupling influences greatly on the measurement correctness. Measurement errors produced from inductive coupling could be reduced by the arrangement methods of auxiliary electrodes. Right angle or P-E-C order arrangement methods were effective to reduce the inductive coupling and the decrease degree of measurement error was analysed as quantitative through an experiment.