Design of Tuned Mass Damper and Hybrid Tuned Mass Damper for a 76-story Benchmark Building to Alleviate Wind Response

76층 벤치마크 건물의 풍응답 제어를 위한 TMD 및 HTMD 설계

  • 민경원 (단국대학교, 건축공학과) ;
  • 박지훈 ((주)마이다스 아이티) ;
  • 김홍진 (단국대학교, 내진/리모델링 연구센터) ;
  • 김형섭 (단국대학교, 건축공학과) ;
  • 정란 (단국대학교 건축공학과)
  • Published : 2003.10.01

Abstract

The design and performance of HTMD(hybrid tuned mass dampers) are evaluated for the response control of a md excited 76-story benchmark building. When a HTMD utilizes active control forces, the optimally designed TMD (Tuned Mass Damper) generates the modal separation at the first natural frequency resulting in difficulties for applying active control forces additionally. Whereas, the modal separation does no occur if the un is designed with the non-optimally designed TMD is used. Therefore, the response control performance of the HTMD with a non-optimally designed TMD is better that one with an optimally designed TMD. Further, the non-optimally designed TMD has an advantage of smaller stroke than the optimally designed TMD relieving the difficulty of limited strokes.