Investigation of the Feasibility of a Bus-bar coupled SFCL in the 154 kV KEPCO Grid

154 kV 초전도 한류기 모선연계 적용 연구

  • Published : 2003.10.01

Abstract

Applicability and economical feasibility of a Superconducting Fault Current Limiter (SFCL) have been investigated using the PSS/E simulation for a bus bar coupling at the real 154 ㎸ KEPCO power grid near Seoul. For the investigated substation, the maximum fault current exceeds the interruption rating of 4 circuit breakers (CB) out of 9 installed in the substation. The simulation showed that a SFCL installed in the bus tie position effectively limits the fault currents to save 4 CBs, which are to be replaced by ones of gloater interruption rating, otherwise. We suggest that the optimum resistance of the SFCL be 10 Ohm for the given grid.