Proceedings of the Korean Institute of IIIuminating and Electrical Installation Engineers Conference (한국조명전기설비학회:학술대회논문집)
- 2003.11a
- /
- Pages.373-376
- /
- 2003
Frequency relativity of soil resistivity
대지저항률의 주파수 의존성
Abstract
A new method measuring soil resistivity in frequency range of 5-500[KHz] using variable frequency inverter was presented, and soil resistivity was analysed by resistive and reactive components on the basis of magnitude and phase of measured ground impedance. The test lead arrangement was proposed to reduce the inductive coupling in test circuit for measuring the soil resistivity. The frequency dependence of soil resistivity was mainly caused by the inductive current flowing through grounding conductors over the frequency of 70[KHz].
Keywords