Distributed N+X Redundant UPS System

분산형 N+X 리던던트 UPS 시스템의 개발

  • Published : 2003.07.01

Abstract

This paper presents a non-electrical isolated Prototype of N+X redundant UPS with two-quadrant converter. Proposed topology has multi-functions of battery charge and discharge regulation, operates with a near unity input power factor, compensates unbalanced voltage on U bus capacitors, and regenerates the circulating active power among the inverters into battery or grid. And furthermore, this system adopts a novel wireless parallel operation algorithm of N+X redundant UPS system with no control interconnections. Simulation and experiment results are provided in this paper to prove the validity of proposed topology and wireless control algorithm.

Keywords