배전계통에 분산전원 연계시 전압강하에 의한 민감부하의 피해를 고려한 보호협조 연구

A Study on the Coordination Scheme Considering the Loss of Sensitive Load by Voltage Sag at Distribution System Interconnected Dispersed Generation

  • 발행 : 2003.07.21

초록

Recently, the concern of power qualiaty problem is increasing. Especially, Voltage quality problem have been increased important problem. Electronic device was affected by voltage sag. So, sensitive load that included many electronic Device was affected by voltage sag. also, it may have economic loss. In this paper, we argue the coordination scheme considering the loss of sensitive load. The coordination device of distribution system for instaneous fault is recloser and sectionalizer, But, the fault clearing time of recloser is more than 2 seconds. So, voltage sag generates long time that affected sensitive load. HS(high speed switchgear) has fast fault clearing time(0.015s) that not affected sensitive load. Therefore, the coordination applied HS is used. The proposed schemes are proved and evaluated by a case study using PSCAD/EMTDC simulation.

키워드