A study on analysis of DVR(Dynamic Voltage Restorer) in electric traction network by using the PSCAD/EMTDC

PSCAD/EMTDC를 이용한 전기철도급전계통에 DVR(Dynamic Voltage Restorer)해석에 관한 연구

  • Published : 2003.07.21

Abstract

The electric traction load is quite differ from general power system load which is single-phase, high-speed heavy load receiving power from 3-phase power system and also has variable load characteristics over time and space. Therefore, there are inevitably power quality problems such as steady state or transient voltage drop, voltage imbalance and harmonic distortion. In addition, it is expected that transient voltage sag could affect the safety of feeding system. Thus, in this paper transient analysis and voltage sag compensation of AT(Auto Transformer) feeding system are studied. The fault study of traction network is analysed by using PSCAD/SMTDC simulation tool. In addition, application of DVR in electric traction system is proposed to compensate the voltage sag of traction network which is occurred by the fault of utility source. The results of fault study will be a useful research works for operation and setting of electric traction relay. Also, it can be shown that application of the DVR in electric system is very useful to compensate the voltage sag from the result of related simulated work. The results of study will be a useful research works for management and planning of power quality in electric traction system.

Keywords