대한전기학회:학술대회논문집 (Proceedings of the KIEE Conference)
- 대한전기학회 2003년도 하계학술대회 논문집 A
- /
- Pages.33-35
- /
- 2003
고압 커패시터 투입시 수용가측 엘리베이터 정지사례 분석
Case Study of Power Factor Correction Capacitors On Upseting Elevator
- 발행 : 2003.07.21
초록
Capacitor switching is essential for the economic operation, and proper voltage control of KOREA electric utility distribution system. Voltage transients produced by capacitor switching (around 2.0 per unit at substation and 2.5 or less per unit at customer site, and lasting less then 1ms) do not have the magnitude or duration to interfere with the operation of computers, but they do disrupt the operation of adjustable speed drivers. The result of our research, ASD manufacturers should team from the computer industry and design products that will operate satisfactory in the electrical envelopment in which they will be placed. In this case history, the inductors on the input to ADSs in order to prevent nuisance tripping from capacitor switching(and other causes within the apartment) proved to be an effective, low-cost solution.