고압유도전동기의 절연상태 평가

Evaluation of Insulation Condition for High Voltage Induction Motor

  • 발행 : 2003.07.21

초록

This test was performed to assess the insulation deterioration condition of the stator winding of 3.3kV class induction motors which have been in service for 15 years after being installed in 1988. The insulation diagnostic tests include resistance, polarization index(P.I). dissipation factor(${\Delta}tan{\delta}$) and maximum partial discharges(Qmax). The results of diagnostic tests were compared to the visual inspection in overhaul.

키워드