고압전동기 고정자 권선의 운전중 부분방전 분석

Analysis of On-Line Partial Discharge in High Voltage Motor Stator Windings

  • 발행 : 2002.05.17

초록

During normal operation, partial discharge(PD) tests were performed using turbine generator analyzer(TGA) in high voltage motor. Epoxy-mica couplers are installed at motor terminal and analyzed PD signal using TGA. #A motor stator insulation is good because small partial discharges are detected PD pattern show that PD occurs in insulation. PD of #B motor is larger than that of #A motor and PD pattern show that positive PD larger than negative PD. It means that PD occurs between insulation and slot. And A phase PD magnitude of #B motor is large and high compare with any other phase. Therefore wedge, core and slot of #B motor need to check and repair.