A Study on the Economical Design of Low-Voltae feeder Considering the temperature character

온도특성을 고려한 저압간선의 경제적인 설계기법에 관한 연구

  • 최홍규 (홍익대학교 전기공학과·전기설비연구소) ;
  • 조계술 (홍익대학교 전기공학과·전기설비연구소)
  • Published : 2002.11.01

Abstract

A size of low-voltage conductor cables is determined by the voltage drop of a system, the cable impedance and the cable ampacity based on temperature correction factor in accordance with the condition of cable installation. Therefore, the proper temperature correction factor according to the condition of cable installation should be applied to determining the cable ampacity and also the skin effect and proximity effect, along with the kind and size of conductor and the condition of cable installation, should be properly considered to analyze the proper value of resistance and the reactance of the conductors. This paper addresses the systematic design flow for determining the size of low voltage level conductor cables in calculating the temperature character where error should be minimized in comparison with the general formula and which can be applied in design work for determining the size of conductor cables.

Keywords