Proceedings of the Earthquake Engineering Society of Korea Conference (한국지진공학회:학술대회논문집)
- 2002.09a
- /
- Pages.155-162
- /
- 2002
Seismic Reliability Evaluation of Electric Power Transmission Systems in Low and Moderate Seismicity Regions
중약진 지역에서의 전력송전시스템의 지진재해 신뢰성 평가
Abstract
A technique for the seismic reliability evaluation of electric power transmission systems(EPTS) adapted to ground motion characteristics of Korea has been developed to evaluate reliability indices corresponding to the whole system and to each node within. A network model with nodes and links for EPTS has been established, and a seismic substation-fragility curve obtained from seismic fragilities of power system facilities has been derived. A point source model, the doubly truncated Gutenberg-Richter relationship, and earthquake intensity attenuation formula have been applied to simulate seismic events. Using Monte-Carlo simulation method, the seismic reliability of EPTS is evaluated and, it appeared that seismic effect on EPTS in low and moderate seismicity regions has to be considered.
Keywords