절연파괴 특성을 이용한 Epoxy 복합체의 전기적 열화 분석

Analysis of Electrical Degradation in Epoxy Composites by Dielectric Breakdown Properties

  • 최철호 (동신대학교 전기전자공학부) ;
  • 박용필 (동신대학교 전기전자공학부) ;
  • 임중관 (동신대학교 전기전자공학부)
  • 발행 : 2002.07.01

초록

The dielectric breakdown of epoxy composites used for transformers was experimented and then its data were simulated by Weibull distribution probability. First of all, speaking of dielectric breakdown properties, the more hardener increased the stronger breakdown strength at low temperature because of cross-linked density by the virtue of ester radical. The breakdown strength of specimens with filler was lower than it of non-filler specimens because it is believed that the adding filler forms interface and charge is accumulated in it, therefore the molecular motility is raised and the electric field is concentrated. In the case of (idled specimens with treating silane, the breakdown strength become much higher Finally, from the analysis of weibull distribution, it was confirmed that as the allowed breakdown probability was given by 0.1[%], the applied field value needed to be under 21.5 MV/cm.

키워드