Wireless Parallel Operation Control of N+1 Redundant UPS System

독립제어구조를 갖는 N+1 모듈형 UPS 시스템의 병렬운전

  • Published : 2002.07.01

Abstract

In this paper, a novel wireless parallel operation algorithm of N+1 redundant UPS system with no control interconnections is presented. The load sharing of multiple UPS modules are controlled by Q-V droop and $P-\delta$ droop algorithm. This algorithm compensates for inverter parameter variation and line impedance imbalances with wireless auto-tuning method. And to increase the reliability of transient characteristic under parallel operation, a virtual injected Impedance is proposed to decrease a circulation current between inverter modules. Simulation results are provided to prove the novel wireless algorithm.