Abstract
A computational approach of the arc quenching process in GCB was developed. it is capable to calculates the thermodynamic quantities of the gas as a function of time taking into account of all spaces concerned with the arc quenching. Basically using so-called FLIC method, this program adoptes 'Simplified Enthalpy Arc Model', which is somewhat modified. And, to examine whether our works were done properly, it was simulated the whole process of the arc quenching that is based on self-flow generation phenomena/current interruption in a thermal expansion type circuit breaker. This program was verified by experiments, both showed fairly good agreement.