초광대역과 단일주파수(협대역) UHF 부분방전 검출기법 비교

Ultra-wide bandwidth versus narrow bandwidth PD detection techniques for UHF partial discharge monitoring system

  • 박기준 (전력연구원 전력계통연구실) ;
  • 구선근 (전력연구원 전력계통연구실) ;
  • 윤진열 (전력연구원 전력계통연구실)
  • 발행 : 2002.07.10

초록

Ultra-wide bandwidth (UWB), narrow bandwidth (single frequency), and a combination of both technologies have been studied for the ultra-high frequency (UHF) partial discharge (PD) monitoring system as a detection scheme. We have experimentally compared those detection methods using a mock-up of 362 kV class single phase gas-insulated switchgear (GIS) and a stable PD source. A rolling-ball type PD cell that produces PDs of about 10 pC, is placed at one end of the GIS. An internal UHF PD sensor was attached several meters away from the PD source. The PD spectrum was measured up to 3 GHz. A useable bandwidth of more than 1 GHz was used to measure UWB signals from the PD. To simulate the narrow bandwidth scheme a bandwidth of 100 kHz centered at several different frequencies was used.

키워드