Investigation and Countermeasure of P.T Ferroresonance in the 154kV GIS Substation

154kV GIS 변전소 P.T. 철공진 규명 및 방지대책

  • Published : 2002.07.10

Abstract

This paper describes the analysis resulates on the P.T ferroresonance at 154kV GIS(Gas Insulated Substation) by EMTP(Electromagnetic transient program). We had simulated the PT ferroresonance between a potential transformer(PT) and open circuit braker's grading capacitance. The ferroresonance leads to very large power frequency overvoltage on PT bus and subsequent insulation failure. The damping circuit connected on the secondary winding were considered in the model. The actual countermeasure include a saturable inductor and a resistor series mounted, but the 2 ohms of damping resistance was used in the computational model.