Analysis of voltage sag effect at load side during fault according to change of power system condition

계통조건(系統條件) 변경(變更)에 따른 고장시(故障時) 부하측(負荷側)의 순간전압강하(瞬間電壓降下) 영향분석(影響分析)

  • Published : 2002.07.10

Abstract

In this paper, we analyze about voltage sag effect at load side during fault according to change of power system condition. through the case studies, we find that there is no close connection between substation bus transfer and voltage sag during fault. however, we find that other feeder connecting with the faulted transmission is directly affected by fault type and magnitude, therefore, the main subject can be divided into the utility and customer side countermeasures, utilities concentrate their effort to prevent the faults and to modify the fault clearing practice in power system. however, the faults in power system can never be completely eliminated. therefore, customer side solutions usually involve the power conditioning equipment for sensitive loads aiso, we investigate that the several methods to reduce the number and severity of voltage sag and to dull the sensitivity of equipment for voltage sag have developed. moreover, about SEMI, the industry association for the semiconductor two voltage sag immunity standards.(SEMI F47, SEMI F42) The simulation is accomplished by PSS/E 26.