Abstract

The effort for measuring the rotor vibration caused by the short of rotor winding or air-gap eccentricity has been carried on. This paper introduces on-line vibration monitoring technologies using search coils to measure flux for synchronous generators. A 3,300/6,600 (V), 150 [kW] synchronous generator is built, and search coils are designed and inserted in the wedges. Furthermore, air-gap eccentricity is analyzed by finite element method and compared with experiment tests. Induced voltages caused by different air-gap eccentricity on the search coils are compared as well.