Selection of Motor Starting Method by Numeric Simulation

기동시뮬레이션 방법에 의한 유도전동기 기동방식 선정

  • 장중구 (서일대학, 상진기술엔지니어링(주)) ;
  • 서상진 (상진기술엔지니어링(주)) ;
  • 이민용 (상진기술엔지니어링(주))
  • Published : 2002.07.10

Abstract

Since a squirrel cage induction motor by NEMA Design types is designed to withstand full-voltage starting, direct starting method can be the most economical one. Starting a squirrel cage motor from standstill by connecting it directly across the line may allow inush currents of approximately 500-600% of rated current at lagging power factor of 35-50%. For many of the large motors, the starting inrush current may be great enough to cause voltage dips, which may adversely affect the building's lighting system. Electric utilities also have restrictions on starting currents, so that voltage fluctuations can be held to prescribed limits. Therefore the need for choosing the most appropriate method of motor starting is quite essential. In this paper, we proposed a plan for the selection of the most appropriate motor starting method, first by way of numeric simulation using manufacturer's data and second by way of actual experience. So far, more often than not, the selection of motor starting method has been accomplished only as regards to the capacity of the motor and the frequency of starting and stopping. But nowadays such high-tech apparatus as soft starters are being developed, and we are on the position to give more attention to clarify the way of selection of the motor starting method.

Keywords