A Study on High Impedance Fault Detection using Lifting Scheme

Lifting을 이용한 고저항고장 검출에 관한 연구

  • 홍대승 (광운대학교 제어계측공학과) ;
  • 임화영 (광운대학교 제어계측공학과)
  • Published : 2002.07.10

Abstract

The research presented in this paper focuses on a method for the detection of High Impedance Fault(HIF). The method will use the Lifting and neural network system. HIF on the multi-grounded three-phase four-wires primary distribution power system cannot be detected effectively by existing over current sensing devices. These paper describes the application of lifting scheme to the various HIF data. These data were measured in actual 22.9kV distribution system. Wavelet transform analysis gives the frequency and time-scale information. The neural network system as a fault detector was trained to discriminate HIF from the normal status by a gradient descent method. The proposed method performed very well by proving the right state when it was applied staged fault data and normal load mimics HIF, such as arc-welder.

Keywords