한국전기전자재료학회:학술대회논문집 (Proceedings of the Korean Institute of Electrical and Electronic Material Engineers Conference)
- 한국전기전자재료학회 2001년도 춘계학술대회 논문집 유기절연재료 전자세라믹 방전플라즈마 연구회
- /
- Pages.221-224
- /
- 2001
다양한 결함으로부터 발생되는 절연열화를 검출하기 위한 새로운 접근기법으로써의 카오스 분석
CHAOTIC ANALYSIS OF PARTIAL DISCHARGE (CAPD) AS A NOVEL APPROACH TO INVESTIGATE INSULATION DEGRADATION CAUSED BY THE VARIOUS DEFECTS
- 발행 : 2001.05.11
초록
In connection with the monitoring of insulation degradation of large power apparatus in order to predict their unexpected service failures, a statistical treatment, such as phase resolved partial discharge analysis(PRPDA), has been established for the on-line monitoring system during the past decades. However, this method has shown some inconveniences to distinguish the nature of the PD source in power apparatus. In this regard, a novel approach based on the chaotic analysis(CAPD) is proposed describing the fundamental ideas, outcomes and different view points from conventional PRPDA. In order to make a model for the possible defects causing sudden failures in service, several types of specimen were prepared. And partial discharge signals, originated from those samples, were measured and analysed by means of PRPDA and CAPD respectively. Throughout this paper, it seems that the correlation between the consecutive PD pulses depending on the nature of PD could be investigated by CAPD. Therefore, it could be considered that the nature of PD source can be distinguished more distinctively when the PRPDA is combined with CAPD.