The Estimation of Outdoor Insulation According to the Concentration of Surface Discharge

표면방전의 집중에 따른 옥외용 설비의 성능평가

  • 임장섭 (목포해양대학교 전자통신공학부) ;
  • 정승천 (목포해양대학교 제어계측공학과) ;
  • 이진 (목포해양대학교 제어계측공학과) ;
  • 노진양 (한국전력공사 신광주 전력소)
  • Published : 2001.05.11

Abstract

The conventional tracking testing as IEC-60587 is widely used in surface aging measurement of outdoor insulator because those testing can carry out very short time in Lab-testing. Also IEC-60587 testing is able to offer the standard judgement of relative degradation level of outdoor HV machine/system. Therefore it is very useful method compare to previous conventional tracking testing method and effective Lab-testing method. But surface discharges(SD) have very complex characteristics of discharge pattern so it is required estimation research to development of precise analysis method. In recent, the study of IRR-camera is carrying out discover of temperature of power equipment through condition diagnosis and system development of degradation diagnosis. In this study, SD occurred from procelain insulator, used 22.9[KV] distribution, is measured with partial temperature distribution in real time, the degradation grade of SD is analyzed through produced patterns in SD concentration according to applied time.

Keywords