냉.온열 동시 제조시스템의 성능분석(I)-Simulation

Performance Analysis of Simultaneous Heating & Cooling Water Making System(I)-Simulation

  • 박성룡 (한국에너지기술연구원) ;
  • 박준택 (한국에너지기술연구원) ;
  • 안영훈 (충남대학교 기계설계공학과 대학원)
  • 발행 : 2001.06.27

초록

In this study, the performance of the simultaneous heating & cooling water making system using R134a was investigated by simulation. The most important effect upon heating COP was intermediate pressure depending on input water temperature. With the input water temperature of $10^{\circ}C\;and\;20^{\circ}C$, optimum intermediate pressure were 923 and 1040kPa, respectively. At that optimum intermediate pressure, the maximum heating COP of the system operated between $0^{\circ}C$ evaporating temperature and $70^{\circ}C$ condensing temperature were 4.15 and 3.83. With installation of the subcoolers in high or low pressure section, the system COP was increased by reducing the refrigerant mass flow rate. Under the optimum pressure and $10^{\circ}C$ input water temperature, it was found that heating COP was maximized when the low-subcooler and high-subcooler capacity rate were taken by 14% and 13%, respectively.

키워드