Investigating Dynamic Characteristics on Support Base for IPB Duct System and Reducing Vibration for IPB Duct

IPB 덕트의 진동저감과 기초에 대한 동특성 고찰

  • Published : 2001.11.01

Abstract

Because of resonance between natural frequency of the second floor base for IPB(Isolated Phase Bus) duct supports in a power plant and operation frequency of the turbine, there was high amplitude vibration on IPB duct. To reduce vibration of IPB duct, Firstly it was set a FEM model to seek the mode shape for the concrete structure. Secondly, it was carried out dynamic analysis for the FEM model. Lastly, because the natural frequency of the concrete structure could not be changed, it was changed supports position for the IPB duct near to beams. It resulted in reducing vibration of IPB duct.

Keywords