대한전기학회:학술대회논문집 (Proceedings of the KIEE Conference)
- 대한전기학회 2001년도 추계학술대회 논문집 전력기술부문
- /
- Pages.333-335
- /
- 2001
AT 철도 급전계통에서의 고장점 표정 알고리즘
Algorithm for Fault Location in AT Feeding Railway System
- Seo, Jae-Beom (Dept. of Electrical Eng. Myongji University) ;
-
Kang, Sang-Hee
(Dept. of Electrical Eng. Myongji University) ;
-
Lee, Seung-Jae
(Dept. of Electrical Eng. Myongji University) ;
- Jung, Byung-Tae (P&C Technologies Co., Ltd)
- 발행 : 2001.11.16
초록
In this paper, an algorithm for fault location in Auto Transformer(AT) Feeding Railway system is presented. If a fault occurs at the AT feeding circuits of electrical railway system, it is very important to find fault location and to remove it immediately for the purpose of ensuring safety for transportation. Because the characteristics of reactance-distance are not linear, only using one terminal signals to give fault distance is difficult. In this paper, first, using the KVL, 4 voltage equation are obtained. Secondly, eliminating voltage a distance equation which consists of currents at rail and line parameters including mutual effects.
키워드