전력설비 절연유 열팽창 계산식 개선에 관한 연구

A study on the improvement of the thermal expansion formula of the insulating oil in electric facilities

  • 발행 : 2001.11.16

초록

The transformer and the OF cable are cooled and insulated by insulating oils in their body. The insulating oil expands or contracts with the heat transfer according to the operating conditions of the electric facilities. So we install the $N_2$ gas tank connected with the insulating oil system to overcome the change. The change of the insulating oil volume for the operation temperature range must be calculated to decide the $N_2$ gas volume and to set the alarm point for safe operation. It is known that this change is proportional to the temperature change and to the insulating oil volume if the temperature change is small enough.[1][11] However this proportional formula has been accepted generally in the design of electric facilities for wide operation temperature range such as $40^{\circ}C{\sim}125^{\circ}C$. Hence, it makes large errors in calculation which car result in serious damage against safe operation of the electric facilities. This paper presents a improved method of calculating the accurate change of the insulating oil volume to insure the safe operation of electric facilities.