Deterioration Diagnostic Techniques for Power Facilities by Analyzing Pulse-Height of leakage current

누설전류 파고분석에 의한 전력설비의 열화진단 기술

  • 한주섭 (한국해양대학교 전기공학과) ;
  • 김명진 (한국해양대학교 전기공학과) ;
  • 손원진 (한국해양대학교 전기공학과) ;
  • 길경석 (한국해양대학교 전기공학과)
  • Published : 2001.10.01

Abstract

This paper proposes a new deterioration diagnostic technique for power facilities by analyzing the pulse-height analysis of leakage current. Until now, various deterioration diagnostic techniques to prevent power system failures by deterioration of power facilities are suggested, and most of which measures leakage current amplitude only as a estimation parameter. In this experiment, it is known that the pulse heights of the leakage current are increased according to deterioration progress as well as there comes remarkable changes in pulse height distribution thereto. Therefore, the use of pulse height distribution in deterioration diagnostic technique makes more accurate diagnosis than the conventional method by using only leakage current value. From the application test, it is confirmed that the proposed technique has sufficient performance to diagnose deterioration of power facilities.

본 논문에서는 누설전류 파고분석을 이용한 전력선비의 새로운 열화 진단법을 제안하였다. 현재까지 여러가지 열화 진단법이 제안되었으며, 평가요소로 누설전류의 크기만을 이용하는 것이 일반적이었다. 본 연구에서는 피뢰기, 케이블 등의 전력설비들이 열화가 진전됨에 따라 누설전류의 파고분포도 크게 달라짐을 알 수 있었다. 따라서 전력설비의 열화진단에 누설전류의 파고분포를 이용하면 기존의 누설전류의 크기만을 이용하는 방법보다 더 정확한 평가가 가능하다. 피뢰기, 케이블을 이용한 여러 가지 적용실험으로부터 제안한 열화 진단법은 충분한 성능이 있음을 확인하였다.

Keywords