Chaotic Analysis of Partial Discharge (CAPD) - A novel approach to identify the nature of PD source

Chaos 이론을 이용한 부분방전 신호분석(CAPD) - 결함 종류 판별을 위한 새로운 접근 방법

  • 임윤석 (한양대학교 전자전기제어계측공학과) ;
  • 구자윤 (한양대학교 전자전기제어계측공학과) ;
  • 김성홍 (순천청암대학 전기설비과) ;
  • 이전선 (한양대학교 전자전기제어계측공학과) ;
  • 최재옥 (한양대학교 전자전기제어계측공학과) ;
  • 윤정훈 (한양대학교 전자전기제어계측공학과) ;
  • 마지훈 (한양대학교 전자전기제어계측공학과)
  • Published : 2001.09.01

Abstract

In connection with the monitoring of the insulation degradation of large power apparatus in order to predict their expected service failures, a statistical treatment, such as phase resolved partial discharge analysis (PRPDA), has been established for the on-line monitoring system during the past decades. However, this method has shown some inconveniences to identify the nature of the PD source in power apparatus. In this regard, a novel approach based on the chaotic analysis (CAPD) is proposed describing the fundamental ideas, outcomes and different viewpoints from the conventional PRPDA. As a model for the possible defects causing sudden failures in service, three types of specimen are prepared. And partial discharge signals, originated from those samples, are measured and analyzed by means of CAPD. Throughout this work, it seems that the correlation between the consecutive PD pulses, depending on the nature of PD, could be clarified by CAPD. Thereffre, it could be considered that the nature of PD source can be identified more distinctively when the CAPD is combined with PRPDA.

Keywords