Analyses of Leakage Magnetic Field and Leakage Inductance in Current Transformers by 3-D Integral Methods

3차원 적분법을 이용한 변류기의 누설 자계 및 누설 인덕턴스 해석

  • Published : 2001.07.01

Abstract

This paper presents leakage magnetic field and leakage inductance calculations in current transformer by means of 3-D Integral methods. From the distribution diagram of leakage magnetic flux to be analyzed using program called TRACAL3, it confirms a parallel to the winding axis direction of the leakage flux lines in the air gap between the windings. The leakage inductances L$\sub$r1/ and L$\sub$R2/ of the primary and secondary windings were calculated, their values are 4.23 mH and 0.49 mH, respectively. They are also similar to the measured values of the leakage inductances for the experimental verification, 4.06 mH and 0.47 mH.

Keywords