Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 2001.07a
- /
- Pages.47-50
- /
- 2001
Problems and Improvement Method of Grounding System in Electrical Facilities
건축전기설비에 적용되는 접지시스템 문제점과 개선방안
- Chung, Young-Ki (Soongsil Univ.) ;
- Kwak, Hee-Ro (Soongsil Univ.) ;
- Shin, Hyo-Sub (Hanyang TEC.) ;
- Chung, Chun-Byoung (Shinhan Co.) ;
- Nam, Taik-Joo (KAPS Ministry of Commerce Industry and Energy)
- Published : 2001.07.18
Abstract
Presently the Korean grounding system uses TN system, multi-grounding method with TT independent grounding method. Nevertheless TN system can't exist with TT system in the technological terms. If they coexist, it causes ground-fault circuit not to operate, and brings about different electrical potential rise by customer system. It brings about serious problems for safety. This paper aims for improving method of grounding system based on the technical analysis on instances in foreign countries and Korea. Almost standards and construction manner were apt to be internationalized after WTO/TBT agreement was concluded. The internal grounding systems should meet the international criteria and reliability for safety, and be provided with technologically impeccable standards.