Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 2001.07c
- /
- Pages.1783-1785
- /
- 2001
Artificial line for short-line fault test
근거리선로고장전류 차단시험용 Artificial line
- Park, Seung-Jae (Korea Electrotechnology Research Institute) ;
- Rhyou, Hyeong-Kee (Korea Electrotechnology Research Institute) ;
- Kang, Young-Sik (Korea Electrotechnology Research Institute) ;
- Koh, Heui-Seog (Kyungnam Univ.)
- Published : 2001.07.18
Abstract
With the 4-MJ synthetic testing facilities completed, KERI can perform the circuit breaker testing up to 420 kV, 50 kA ratings. The short-line fault test is one of the necessary test items which are required for the circuit breaker, and in order to perform the short-line fault test KERI(Korea Electrotechnology Institute) has used the "new artificial line" which has small dimension and is easy to generate the saw-tooth wave. This paper describes the following items of the new artificial line. -Description of 4-kinds of artificial lines and determination of the circuit parameter of artificial line. -TRV characteristics of saw-tooth waves for each circuit. -KERI's artificial line.
Keywords