Influence of Contact and Wall Material on Arc Interruption in Air

기중 아크 차단에 대한 접점 및 소호 재료의 영향

  • 이상엽 (LG산전 전력연구소, 전력기기사업부) ;
  • 박홍태 (LG산전 전력연구소, 전력기기사업부) ;
  • 오일성 (LG산전 전력연구소, 전력기기사업부) ;
  • 이경행 (LG산전 전력연구소, 전력기기사업부)
  • Published : 2001.07.18

Abstract

Air arc interruption used in low rated voltage breaker, ACB and MCCB, have used the arc chamber composed of metal plates and insulating laminates which supposed these mechanically. and geometry and materials of arc chamber are very different by breaker manufacturer. These breakers have required to be smaller and to interrupt higher current by user. therefore the arc chamber geometry and material in breaker have been small, complex and various. The purpose of this study is to examine the effects of insulating laminates and contact materials on air arc interruption. Contacts were surrounded by a rectangle chamber of insulating laminates. Contact concoctions were composed of AgW, AgCdO that have used in low rated voltage breaker, and insulating laminates were polyester, epoxy. We found strong dependance of arc voltage on insulating material. The ablated vapor on polyester increased arc voltage that was useful in air arc interruption.

Keywords