Performance evaluation of PF-condenser adapted to Large Size air-conditioner

대형 에어컨에 적용된 PF열교환기의 성능평가

  • Published : 2000.04.20

Abstract

In this study, We evaluated the Performance of PFC and the system performance of large size air-conditioner applying to outdoor condenser. PFC can meet the same cooling capacity in 40.42% of volume to fin-tube condenser. Although the fin-tube condenser requires 3600g of refrigerant charging, PFC requires 1700g, 1800g, 1900g, 2000g refrigerant charging for each 2.0mm, 2.5mm, 3.0mm and 3.5mm fin pitches. Difference of condensing and evaporation pressure is the biggest point 2.0mm fin pitch and the smallest point 2.5mm fin pitch.

Keywords