Analysis of Fault Current for the Electric Railway Grounding System
전기철도 접지시스템 혼용 운용시 고장전류 해석
Abstract
This study is carried out using a circuit model approach. First, the self and shunt impedances of all the conductors in the rail system and the mutual impedances between different conductors are computed. Then, a circuit representing the both rail systems at interfaces including the rails, feeders, protection wires, contact wires, ground wires is built. Auto-transformers in the system are also represented in the circuit model. The circuit model is then 1]recessed using a circuit solver based on a double-elimination method. Several different scenarios are analyzed, including the load conditions and a few fault conditions with different fault locations. The effect of the buried ground wires is also analyzed by comparing the results with and without the presence of the ground wires. The analysis procedure presented in the paper demonstrated an accurate way of computing fault current distribution and EMC at interfaces between both systems. The results presented in the paper can be used as a reference for estimating interference levels in similar rail systems.
Keywords