Proceedings of the Korea Concrete Institute Conference (한국콘크리트학회:학술대회논문집)
- 2000.10b
- /
- Pages.1057-1062
- /
- 2000
A Study on Construction Quality Inspection of Field use Concrete
현장 타설용 콘크리트의 시공품질 검토를 위한 연구
Abstract
The purpose of this study is to practice the method which can estimate 28-days strength of concrete in advance. This method is made for reliant quality control. Based on existing experiment, concrete that flyash added and normal concrete are placed into wall structure, and it is examined the difference between experiment use concrete and field use concrete. The result of this study are as follows : 1) Core test specimen have 10% lower strength to standard curing specimen. 2) At 28-days accelerated strength by microwave, average 35% in normal concrete, average 23% in flyash added concrete. 3) At coefficient of determination between compressive strength and accelerated strength, 0.84 in normal concrete core, 0.86 in standard curing normal concrete, 0.86 in flyash added concrete, 0.90 in standard curing flyash added concrete.