The effectiveness of noise reduction devices for transformer noise control of Power Plants
발전소 변압기 소음저감 대책의 유효성
- Published : 2000.06.22
Abstract
Power transformers, air-intakes, stacks in a combined thermal power plant are the main noise sources. Power transformer noise among them has being get a target of public complaint due to 480Hz component of its pure tone. The source is mainly magnetostrictive vibration of the transformer core. The first countermeasures was installing sound barrier on the front of transformer. However, 500Hz, center of the frequency is not reduced. This paper includes the measurements of noise level at the near resident apartment, the identification of noise transfer and the countermeasures for noise sources. Cavity resonance type of noise reduction devices was installed on enclosuring wall of transformers. As a result, the noise level from transformer is reduced about 3dB.