Proceedings of the Korean Society for Noise and Vibration Engineering Conference (한국소음진동공학회:학술대회논문집)
- 2000.11a
- /
- Pages.75-81
- /
- 2000
- /
- 1598-2548(pISSN)
Vibration Reduction of an Air Cooled Heat Exchanger with Axial Flow Fan
축류송풍기 부착형 공냉식 열교환기의 진동 저감
- Published : 2000.11.16
Abstract
Vibration problems induced by an air cooled heat exchanger with axial flow fan were investigated during the operation of a petrochemical plant. Two different studies were done; one was experimental field test and the other was theoretical verification. To find main cause of the blade passing frequency of the fan after installing additional blockage board at the air inlet of the axial fan, the frequency spectrum was measured. The vibrations of the blade passing frequency became higher. The natural frequency of driving support of the heat exchanger was theoretically calculated. It was approximately equal to the blade passing frequency. During the normal operation of the plant, it was impossible to modify the structure of the driving support. Instead, the blade number was increased to reduce vibration level. It increased the ratio of the forcing frequency to the natural frequency of the driving support over the resonance region.