Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 2000.07a
- /
- Pages.477-479
- /
- 2000
An Analysis of Grounding Methods for Safety of Linemen in Distribution Line
배전선로 작업안전을 위한 최적접지 방법 평가
- Lee, H.S. (Korea Occupational Safety Agency) ;
- Choi, S.W. (Korea Occupational Safety Agency) ;
- Ryu, B.H. (Korea Occupational Safety Agency) ;
- Chang, S.H. (Korea Railroad Research Institute) ;
- Kim, J.H. (Hongik University)
- Published : 2000.07.17
Abstract
This paper presents an analysis which compares the effectiveness of different temporary safety grounding methods on working overhead distribution system. The analysis studied direct energization at fault conditions with seven scenarios. The results show that the scenario, single point safety grounding on the working pole with brackets Pairs spaced 2 km apart on both side of a work site is safest grounding method. This can be used to evaluate lineman safety on a overhead distribution systems in Korea.
Keywords